Some Notes On The Thermal Calculations ====================================== Simplifications Made And Their Winter Effects --------------------------------------------- There are a few factors--some trivial and some not--that might affect the validity of the calculations; those effects might be favorable or unfavorable. Here they are. One possible negative is the foam insulation, which was assumed to have a long-term-aged R value of 6.9 the inch. It used to be specified at 7.14 but has been downrated recently, for reasons unknown to me. The 6.9 value was quoted by an experienced installer; a sales rep mentioned 6.8 or 6.75, so the 6.9 might be a little optimistic. Another small negative is the heat that will be lost when the HRV is running. The HRV has an effective recovery of about 60% of the heat that would be lost if the flow were simple infiltration. The flow when the HRV runs is perhaps 150 or 160 cfm, or about 9,300 cubic feet an hour. Its net loss is thus about 2,700 BTUs an hour. It is unlikely that the HRV would run more than an hour or, at very most, two hours a day (shower and cooking time), so the likely loss is 5,000 BTUs or so a day, not a large factor (and controllable in especially cold snaps). Yet another small negative is that there is no allowance for the loss of insulating value owing to any in-wall plumbing or wiring runs in outside walls. Well, first, there is NO plumbing running in any outside wall. Second, there is but the minimum electrical wiring needed to supply outlets numerous enough to meet the insane "Vacuum Cleaner" requirements of the Electrical Code (which, with the built-ins, means none in the west wall). So this is a pretty small negative. A big favorable factor not considered is that nearly half of the house west wall is not actually exposed to outdoor air at the average outdoor temperature but instead to the tank room, at an average temperature about 20 degrees warmer. Moreover, the entire exterior west house wall (including the entrance door) is sheltered from direct outdoor air and so might be a degree or a few degrees warmer, plus will have at least a trivially higher R value (owing to the zero windspeed at the wall surface). Also, no account was taken of the fact that the "attic" space (it's not really an attic, but that's where it's located) will almost surely be warmer than the raw outdoor temperature, and is also wind-protected. Considering the ceiling area, a few degrees difference could mean a bit: every degree the attic is warmer than the raw outside is 1,150 BTUs less heat loss. Another ignored minor possible source of heat gain is the east window, which might be unshaded for a couple of hours a day of sun (10 am - noon, when east sun disappears)--maybe a 1,000 or so extra BTUs if anyone bothers to pull the shades. A final probable plus is the floor heat loss. Simply assigning an R value of 9.2 to bare earth is very conservative. The deep-earth (well-water) temperature should be 50 degrees (it is usually the average annual temperature--about 48 degrees for Ritzville--plus 2 degrees). Thus, assuming for simplicity that the slab itself is essentially transparent to heat, the underslab temperature is the house temperature, an average of 64 degrees. That means that if the slab were infinite in extent, the deltaT across the XPS insulation would be 14 degrees at all points, which implies a 24-hour heat loss through a house-sized section of slab of 40,873 BTUs, compared with the calculated 73,640 BTUs for the average coldest day and 147,281 BTUs for the very coldest day possible. Now the slab is, obviously, NOT infinite in extent and, as everyone knows, the majority of heat loss occurs at or near the perimeter of a slab; that is because the ground adjacent to the slab is not at deep-earth temperature until a depth of 6 to 20 feet. The true physics of heat flow through a slab on grade are immensely complex. Nonetheless, with thick perimeter insulation as is found on this house, the true loss is almost certainly less--and probably materially less--than the calculations show. All in all, one may mentally write the attic off against the HRV, ignore the east window, and write the floor off against the possibility of a lower foam R--leaving the warmer west wall as a substantial error reserve against the rest of the negatives. And, in the tank room, no account has been taken of the fact that plant lighting would be running about two hours a day in the winter, generating perhaps up to a couple of thousand BTUs a day. Tank-Room Freeze Risk --------------------- As the calculations show, the 24-hour average temperature in the tank room on the average coldest day of the year will be 43 to 44 degrees. With over 3,400 gallons of water in the room (the 3,000-gallon tank plus eight 55-gallon drums of water), it requires well over 28,000 BTUs of heat flow to change the temperature even 1 degree, so the daily highs and lows will not be far from the daily average. As the numbers also show, the worst-case 24-hour BTU outflow from the tank room on the very coldest possible day day will be about 70,000 BTU. In reality it would be rather less since, as heat flows out and the temperature drops, the heat outflow would slow; but for simplicity, the calculations show the heat outflow assuming a constant inside temperature equal to the average-coldest-day value. Now, as noted above, with over 3,400 gallons of water in the room, it requires well over 28,000 BTUs of heat flow to change the temperature even 1 degree. With the average coldest-day temperature over 43 degrees, a drop of more than 10 degrees inside would be required to just approach a freezing temperature. Thus, the tank room could easily withstand four consecutive days of the coldest temperatures ever recorded in Ritzville before getting close to freezing. And, in the fantastically unlikely event of such a bizarre cold snap, a mere 1000-watt space heater--a toy--running constantly could produce about 81,400 BTUs a day, far more than offsetting the entire daily loss. House Cooling Notes ------------------- On the average hottest day of the year, assuming for discussion that the sun is 100% blocked by the sunshades, the cooling need to offset internal gains (the average inside can equal the comfortable 72ø outdoor average) is about 86,800 BTUs. If we assume that air is allowed to flow into the house throughout the 16-hour shades-up ("night") period, and that that air is at an average temperature of 10 degrees below the house temperature, the average flow rate needed is about 500 cfm. We can justify guesstimating that average air-temperature differential by assuming that the outdoor temperature varies linearly between the daily high and the daily low and that the outside is down to the house average (72ø) by the time the shades are rolled up, about 6 pm., and that it is back up to the house average by the time they are closed again, about 10 am. Under those assumptions, the average outdoor temperature--the low being 54ø--swings from 72 to 54 and back to 72, and its average is 61 degrees, which is 11 degrees below the presumed house average. The assumptions are pretty loose, but obviously we are at least in the correct order of magnitude using that guesstimated 10-degree cooling potential. To put the values in perspective: 1.0 mph is 88 feet a second; a doorway is 20 square feet; and so a movement of 500 cubic feet a minute through an open door signifies an average breeze through that door of 0.284 mph, which is very certainly not much, hardly over a quarter of a mile an hour average. It would appear that with the entry door opened fully and a good-quality window fan mounted in the TV Room window as an exhaust to pull air into and through the house, summer cooling should be . . . a breeze. Even on the worst-case day, only about 1,300 cfm would need to be moved--a breeze of about three-quarters of a mph. Of course, that assumes the same 10-degree cooling potential, which would not be the case if we still assume an indoor temperature of 72ø; but at worst the house average rises tolerable a few degrees during such a rare heat onslaught. Tank-Room Cooling Notes ----------------------- Left to itself, the tank room has no way to void its slow heat gain in warm months, so it cannot be left to itself. By opening the door at night and placing a small vent fan in the roof of the storage area, we can draw a decent amount of cooling air through the tank room (which is also beneficial to any plants grown there). That requires an intake vent, probably on the south wall somewhere--or an openable window. The cooling need is only for a few cfm (10? 15?), so changing one of the windows to a casement would suffice; the extra infiltration loss in winter should not be material. {end}